Why the wires come in threes.

Stand under a big power line and count the wires. Leave out the thin one or two at the very top, which are there to catch lightning, and the heavy wires come in threes. There are three on one side of the tower, and often three more on the other. The lines along a country road carry three wires across the top of each pole. The cable that feeds a machine in a factory has three thick wires inside it. Follow any of them back far enough and you arrive at a generator with three sets of coils.

A house seems to manage with two wires, so why does everything larger use three? The answer begins with an awkward fact about the wall outlet that chapter 16 walked straight past. The power from an outlet arrives in pulses, with moments of nothing in between.

1. One wave delivers its power in pulses

Chapter 16 drew the voltage of a wall outlet in North America. It climbs to 170 volts one way, swings back through zero to 170 volts the other way, and makes 60 of those swings every second. The chapter then showed that the power a heater takes goes as the voltage multiplied by itself. Set those two facts side by side, and something follows that the label on a kettle never mentions. Twice in every swing the voltage passes through zero, and at those moments the kettle is taking no power at all. At the two peaks of the swing it is taking twice the power on its label.

So a kettle marked 1,500 watts really takes 3,000 watts, then nothing, then 3,000 again, 120 times every second. The 1,500 on the label is the average. The RMS voltage of chapter 16 is exactly the figure that makes this average come out right.

A kettle is untroubled by any of this. Water holds its heat, and the pulses come less than a hundredth of a second apart, which is far too short a time for it to cool. A lamp with a glowing wire inside coasts through the gaps in the same way. A lamp made of light-emitting diodes has no such store of heat, and a cheap one really does blink 120 times a second. The blinking is too fast for the eye, and the slow-motion camera of a phone catches it easily.

For a motor the pulses matter a great deal more. Think of riding a bicycle with one foot. You push hard for part of each turn of the pedals and coast through the rest, and the bicycle surges and sags. An engine with a single cylinder has the same trouble, which is why a lawnmower shakes in your hands and needs a heavy flywheel to carry it from one push to the next. A motor that runs from one wave is pushed 120 times a second, with nothing in between. Its own spinning weight carries it across the gaps, and it hums with the pulses.

Two feet on the pedals, set half a turn apart, smooth the ride. A car engine with six cylinders that fire in turn is smoother still. The same cure works for electricity, and there it works perfectly.

2. Three waves, a third of a swing apart

Picture three separate supplies, each feeding a heater of its own. All three make the same wave, with one difference between them. The second wave reaches each of its peaks a third of a swing after the first, and the third wave a third of a swing after the second. Whenever one heater is passing through a moment of nothing, the other two are busy. Add the three powers together, moment by moment, and the gaps left by each wave are filled in by the other two.

The drawing below shows the voltages on top and the power underneath. Start with one wave, and then press three.

The power of three waves is a level line, with no pulses and no ripple of any size. The gaps are filled exactly. This is a fact about three waves set a third of a swing apart, as firm as the fact that the three corners of a triangle add up to half a turn.

A second fact is sitting in the top half of the drawing, and it turns out to be worth even more. At every moment the three voltages add up to nothing. When the first wave stands at its peak, the other two are each halfway down the other side, and one whole less two halves is nothing.

A bicycle wheel shows why this always works. Stick three bits of tape on the rim, each a third of the way around from the last, and turn the wheel slowly. The height of each bit of tape, measured up or down from the axle, rises and falls as a smooth wave. Whenever one of them is high, the other two are low by just enough to balance it. That balance is the reason a fan with three evenly spaced blades runs without a wobble. The three heights add up to nothing all the way around, and so do three waves that keep the same spacing.

The place a wave has reached in its swing is called its phase. So the three waves are known as the three phases, and the whole arrangement as three-phase power. Electricians have a homelier word for the three wires that carry them. They call them the legs.

3. Three wires do the work of six

Three separate circuits ought to need six wires, since every circuit needs one wire to carry its current out and another to bring it home. Now join the three home wires into one. The current in that shared wire is the sum of the three currents. With three equal heaters, the three currents rise and fall in step with the three voltages, so their sum is nothing at every moment. A wire that carries nothing can be taken away.

leg 1leg 2leg 3nothing flows
Three heaters, one on each leg, with their far ends joined at a common point. Each wire carries its own current out and, at the same moment, part of the other two currents home. The dashed fourth wire runs from the common point back to the supply. With three equal heaters it carries nothing at all.

What remains is three wires carrying three circuits. Each wire is the way out for its own current and, at the same moment, part of the way home for the other two. Half of the metal has been saved, and the power still arrives without a pulse.

That comparison is a little kind to the three wires. Joining the circuits raises the voltage between one wire and the next, and a higher voltage calls for more insulation and more room between the wires. The stricter test sets a three-wire line against a single pair of wires, with the same voltage between wires, the same power delivered and the same loss on the way. The three-wire line still wins. It needs three quarters of the metal that the pair does. On a line that runs for hundreds of kilometers a quarter of the metal is a great deal of money, and it is the reason the wires on the towers come in threes.

In a building the three loads are seldom equal, because lights and outlets are shared out among the legs and people switch them on as they please. There the fourth wire is kept. It carries only the small amount by which the three currents fall short of canceling, and its name is the neutral.

4. A field that turns

The best gift of three waves is to the motor, and seeing it takes one fact from chapter 28. Every electric current is wrapped in a magnetic field. Wind the wire into a coil, and the coil becomes a magnet for as long as the current flows, with a strength that follows the current. Reverse the current, and the two ends of the magnet trade places.

Feed a coil from one wave and you have a magnet that grows, fades, turns itself end for end, and grows and fades again, 60 times a second. Its pull goes back and forth along a single line. A motor needs something to chase around a circle, and a pull along a line gives it nothing to chase and no reason to prefer one direction to the other. This is the deeper trouble with one wave. The motors in fans and pumps that run from a wall outlet carry an extra winding, and often a capacitor as well, whose only job is to imitate a second wave and give the motor a shove in one direction.

Now set three pairs of coils around a ring, a third of a turn apart, and feed each pair from one of the three legs. Each pair still does nothing but pull back and forth along its own line. Because the three take their turns a third of a swing apart, their pulls add up to something that none of them has alone. The sum is a single pull of steady strength whose direction travels around the ring, once for every swing of the supply. Nothing in the ring moves. The magnetism itself goes around.

A crowd at a stadium does the same thing when it makes a wave. Every person only stands up and sits down in place, each a moment after the neighbor, and a wave that nobody is carrying runs all the way around the stands.

Put anything magnetic in the middle of the ring and it is dragged around after the field. The part of a motor that turns is called the rotor. In the commonest motor of all, the rotor is a plain drum of iron with bars of aluminum cast into it. It holds no magnets, and no wire runs to it. The field sweeping past the bars drives currents in them, the currents turn the drum into a magnet, and the drum follows the field around, always a little behind. Nothing touches the rotor except its two bearings, which is why motors of this kind run for decades in pumps, fans, elevators and factory machines. The International Energy Agency reckons that electric motors use more than four tenths of all the electricity the world generates, and much of that passes through motors like this one.

Two more things come free with a turning field. Its speed is set by the supply. On 60 hertz, a motor with one pair of coils for each leg has a field that turns 60 times a second, and motors wound with two or three times as many coils turn at a half or a third of that speed. Its direction is set by the order in which the three legs take their turns. Swap any two of the three wires, and the field and the motor run backward. An electrician who connects a new pump checks which way it turns before leaving, for exactly this reason.

The drawing below looks into the end of such a motor. The dots around the ring are the coils, colored by the leg that feeds them. Each thin arrow is the pull of one pair of coils, and the heavy arrow is the three added together. The bar in the middle stands for the rotor.

5. Losing a leg

Every so often one of the three wires stops delivering. A fuse on one line blows, a contact inside a switch burns away, or a storm brings down one wire of the three. Electricians say that the circuit has lost a leg, and both drawings have a button for it.

Follow what is left. Two wires remain, and two wires make a single circuit, in which whatever current flows in along one wire must flow back along the other. Two legs of a three-phase supply therefore amount to one wave. Every gift of the three waves is withdrawn at the same moment. Press three, with a leg lost in the first drawing, and the level line of power turns back into pulses that fall to nothing twice in every swing. Three heaters joined at a common point deliver half of what they did before.

A motor fares worse, and how much worse depends on what it was doing when the leg was lost.

A motor that was running keeps running. Its two live coils now pull back and forth along a single line, as one wave must. A rotor that is already spinning meets each of those pulls at a moment when it can use it, in the way that a child already swinging can be kept going by pushes from one side only. So the motor turns, weakened, and it growls as it goes. The machine it drives still demands the same work, and the motor answers by drawing more current through its two live legs, close to twice the usual amount. The heat in a wire goes as the current multiplied by itself, so the live coils make three or four times their usual heat. The varnish that insulates their wire can stand that for a matter of minutes.

A motor that was standing still stays still. A pull that goes back and forth along a line favors neither direction, and the rotor only trembles where it stands. A turning motor pushes back against its supply, and a stalled one has stopped pushing, so the current climbs to several times the usual amount. The motor hums loudly and can burn out in less than a minute.

In any installation that was built with care, something steps in first. The box that starts a large motor contains an overload relay. It keeps watch on the current in all three legs, and it opens all three when any one of them carries too much for too long. Many starters add a second relay that looks for a missing leg directly and acts before the heat has begun to build.

The rest of a building feels a lost leg too. Its lights and outlets are shared out among the three legs, so about a third of them go dark while the others carry on as if nothing had happened. Rooms lit beside rooms dark, with the big fans gone quiet, is the mark of a lost leg.

A house in North America has a small version of the same event. The house is fed from just one of the three legs, through a transformer that splits its output down the middle into two halves of 120 volts each. The halves swing opposite to each other, so there are 240 volts between them for the stove and the clothes dryer. When one of those two wires fails, half of the lights and outlets go dark, and the stove and the dryer stop with them.

6. Two voltages from the same wires

Three-phase wiring gives every building two voltages, and the reason is the third of a swing between the legs. Measure from any leg to the common point where the three circuits meet, and you find one voltage. Measure from one leg to another, and you find a larger one. If the two legs swung exactly opposite to each other, as the two halves of a house supply do, the larger voltage would be double. They are only a third of a swing apart, so the two waves pull against each other only in part. The voltage between them comes to 1.73 times the single one, and that number is the square root of three.

In North America a small commercial building has 120 volts from each leg to the common point, for its outlets, and 208 volts between legs, for its larger machines. A big building has 277 and 480. The rows of lights in an office ceiling run on 277, and the motors on 480. Across most of Europe the pair is 230 and 400, and in many countries all three legs come into an ordinary house, where the kitchen stove is connected to every one of them.

When a power line is described as a 345,000 volt line, the figure is the larger of its pair, which is the voltage between two of its wires.

7. Where the three waves come from

All of this depends on three waves that stay exactly a third of a swing apart, hour after hour and year after year. It sounds like a feat of timing, and it takes no timing at all. A generator is a motor run backward. A turbine spins a magnet inside a ring that holds three sets of coils, a third of a turn apart. Each time the magnet sweeps past a coil it pushes a wave of voltage through it. The three coils receive their waves a third of a turn apart because that is where they sit. The spacing of the waves is built into the iron.

On 60 hertz, the magnet of a large steam-driven generator turns exactly 60 times a second, one turn for each swing. Every such machine on the same network turns in step with all the others, and the field in every three-phase motor on the network turns in step with them. From the power station to the last pump, it is as though one long shaft ran through the whole country.

The idea was proved in public in August of 1891. An electrical exhibition was under way in Frankfurt, in Germany, and its organizers arranged for a water turbine on the river Neckar, at the town of Lauffen, to send its power to the exhibition over three copper wires, each thinner than a pencil. The distance was 175 kilometers, far beyond anything that had been attempted, and the wires were run at 15,000 volts. About three quarters of the power that left the turbine arrived in Frankfurt, where it lit lamps and drove the pump of an artificial waterfall. The machines came from two engineers, Mikhail Dolivo-Dobrovolsky in Berlin, who had settled on three waves and three wires a few years before, and Charles Brown in Switzerland. The turning field itself had been described in 1888 by Nikola Tesla in America and by Galileo Ferraris in Italy, each working alone. Within a few years of the exhibition, three wires had become the way the world moves its power, and they have remained so ever since.

8. The arithmetic and a program

one wave             power = its average x (1 + cosine of twice the angle)    from nothing to twice the average
three waves          each one a third of a swing, 120 degrees, after the last
their voltages       v1 + v2 + v3 = 0                                         at every moment
their powers         p1 + p2 + p3 = 3 x the average of one                    at every moment
between two legs     1.732 x one leg, the square root of 3                    120 and 208, 277 and 480, 230 and 400
three equal heaters  watts = 1.732 x volts between legs x amps in each leg
the turning field    turns a second = hertz / pairs of coils on each leg      at 60 Hz: 3,600 or 1,800 or 1,200 turns a minute
three wires          3/4 of the metal of a pair, for the same power, loss and voltage between wires
a leg lost           one wave again. The same work then takes 1.73 x the current and 3 x the heat, or more

The program works out the three voltages at six moments, a twelfth of a swing apart, and adds them up. Beside the sum it prints the power of one wave alone and the power of all three.

#include <math.h>
#include <stdio.h>

static const double PI = 3.14159265358979323846;

/* The three voltages of a three-phase supply at one moment, each a wave one unit tall. */
void legs_at(double turn, double legs[3])
{
    for (int k = 0; k < 3; k++) legs[k] = cos(turn - k * 2.0 * PI / 3.0);   /* each a third of a turn behind the last */
}

/* The power three equal heaters take at that moment, one on each live leg. */
double power_at(double turn, const int live[3])
{
    double legs[3], power = 0.0;
    legs_at(turn, legs);
    for (int k = 0; k < 3; k++) if (live[k]) power += legs[k] * legs[k];
    return power;
}

int main(void)
{
    const int one[3] = { 1, 0, 0 }, three[3] = { 1, 1, 1 };

    printf("moment   leg 1   leg 2   leg 3     sum   power of one   power of three\n");
    for (int step = 0; step < 6; step++) {
        double turn = step * PI / 6.0, legs[3];
        legs_at(turn, legs);
        printf("%4d    %+.2f   %+.2f   %+.2f    %.2f       %.2f            %.2f\n", step, legs[0], legs[1], legs[2],
               fabs(legs[0] + legs[1] + legs[2]), power_at(turn, one), power_at(turn, three));
    }
    return 0;
}

/* It prints:
  moment   leg 1   leg 2   leg 3     sum   power of one   power of three
     0    +1.00   -0.50   -0.50    0.00       1.00            1.50
     1    +0.87   +0.00   -0.87    0.00       0.75            1.50
     2    +0.50   +0.50   -1.00    0.00       0.25            1.50
     3    +0.00   +0.87   -0.87    0.00       0.00            1.50
     4    -0.50   +1.00   -0.50    0.00       0.25            1.50
     5    -0.87   +0.87   +0.00    0.00       0.75            1.50   */
import math

THIRD = 2 * math.pi / 3     # a third of a turn

def legs_at(turn):
    """The three voltages of a three-phase supply at one moment, each a wave one unit tall."""
    return [math.cos(turn - k * THIRD) for k in range(3)]

def power_at(turn, live=(True, True, True)):
    """The power three equal heaters take at that moment, one on each live leg."""
    return sum(v * v for v, on in zip(legs_at(turn), live) if on)

print("moment   leg 1   leg 2   leg 3     sum   power of one   power of three")
for step in range(6):
    turn = step * math.pi / 6
    a, b, c = legs_at(turn)
    print(f"{step:4d}    {a:+.2f}   {b:+.2f}   {c:+.2f}    {abs(a + b + c):.2f}       {power_at(turn, (True, False, False)):.2f}            {power_at(turn):.2f}")

# It prints:
# moment   leg 1   leg 2   leg 3     sum   power of one   power of three
#    0    +1.00   -0.50   -0.50    0.00       1.00            1.50
#    1    +0.87   +0.00   -0.87    0.00       0.75            1.50
#    2    +0.50   +0.50   -1.00    0.00       0.25            1.50
#    3    +0.00   +0.87   -0.87    0.00       0.00            1.50
#    4    -0.50   +1.00   -0.50    0.00       0.25            1.50
#    5    -0.87   +0.87   +0.00    0.00       0.75            1.50
use std::f64::consts::PI;

/// The three voltages of a three-phase supply at one moment, each a wave one unit tall.
pub fn legs_at(turn: f64) -> [f64; 3] {
    [0.0, 1.0, 2.0].map(|k| (turn - k * 2.0 * PI / 3.0).cos()) // each a third of a turn behind the last
}

/// The power three equal heaters take at that moment, one on each live leg.
pub fn power_at(turn: f64, live: [bool; 3]) -> f64 {
    legs_at(turn).iter().zip(live).filter(|(_, on)| *on).map(|(v, _)| v * v).sum()
}

fn main() {
    println!("moment   leg 1   leg 2   leg 3     sum   power of one   power of three");
    for step in 0..6 {
        let turn = step as f64 * PI / 6.0;
        let [a, b, c] = legs_at(turn);
        println!("{:4}    {:+.2}   {:+.2}   {:+.2}    {:.2}       {:.2}            {:.2}", step, a, b, c, (a + b + c).abs(),
                 power_at(turn, [true, false, false]), power_at(turn, [true, true, true]));
    }
}

// It prints:
// moment   leg 1   leg 2   leg 3     sum   power of one   power of three
//    0    +1.00   -0.50   -0.50    0.00       1.00            1.50
//    1    +0.87   +0.00   -0.87    0.00       0.75            1.50
//    2    +0.50   +0.50   -1.00    0.00       0.25            1.50
//    3    +0.00   +0.87   -0.87    0.00       0.00            1.50
//    4    -0.50   +1.00   -0.50    0.00       0.25            1.50
//    5    -0.87   +0.87   +0.00    0.00       0.75            1.50

Read down the last two columns. One wave delivers a different power at every moment, and three together deliver one and a half at all of them.

Try it: count, film and read a label

  1. Count the wires on the next large power line you pass. The heavy ones come in threes, and the thin one at the top is for lightning. Then look at the poles on a quiet street of houses. In North America a single wire often runs along the top. It is one leg of the three, borrowed to feed that street.
  2. Film a lamp with the slow-motion camera of a phone. A cheap lamp made of light-emitting diodes, or an old fluorescent tube, shows the pulses of section 1 as a flicker or as dark bands that crawl across the picture. A lamp with a glowing wire hardly flickers at all.
  3. Find the metal label on a large motor, such as the one on a shop compressor or an air conditioner on a roof. Look for the letters PH and the figure 3 beside them, which stand for three phases. The speed on the label will be a little under 3,600 or 1,800 turns a minute, such as 3,450 or 1,750, because the rotor always runs slightly behind the field.
  4. In the drawing of section 4, press lost a leg while running and watch the heavy arrow. It has stopped going around and only swings, and yet the rotor keeps turning. Then press lost a leg before starting and see why a stalled motor has no way to begin.

Three waves that cancel one another, three wires that carry one another's currents home, and a magnet that turns with nothing moving all come from one decision, which is to space three ordinary waves a third of a swing apart. The next chapter looks at wires that travel side by side, and at what else they cancel.